Is it possible to use the S-Net MPI port as free RS 485 port?

FAQ #100529

Yes, it is possible to use the S-Net MPI port on the PCD3.M5xxx as free RS 485 port (S-Bus or Mode C per example).

 

Requirements
- Firmware Version $12 or higher is needed.
- The port has to be assigned as port 3

Wiring

DSub Pin        Signal
        1                 GND
        3               RxD/TxD-P
        8               RxD/TxD-N

 

Categories

PCD3

Last update: 24.05.2015 21:57

First release: 14.02.2006 14:14

Views: 971

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download