Why does "Sasi Slave" on Port 1 / 0 (RS232) of the PCD3 generate an error?

FAQ #100420

 

Configuration:
PCD3
PCD3.F121 Port 1
or on Port 0 (just with FW $26)

 

 

Problem
When using a Sasi Slave F-Box for the configuration of channel 1 and choosing RS Type RS 232, it will generate an error and the communication will never work. Otherwise the same configuration works on a PCD2.

Reason
There is a difference in the Firmware of the PCD3 which doesn't allow this configuration

Solution
Choose RS Type Default in the Sasi Slave F-Box and it will work.

 