Error LED is on after SASI S-BUS Master IP is implemented. Error Message in History: IP Fail Sasi DBX
FAQ #100401
If there is only one CPU in the project you are not able to asign a SASI S-BUS Master IP.
Problem
An error is assigned after the download of a project with SASI S-BUS Master IP implementation. Error Message in History: IP Fail Sasi DBX.
Reason
If only one CPU is in the project and in the IP Table, the master has no communication partener an therfore it will indicate an error.
Solution
Add a second CPU with TCP/IP configuration to the project (it can be a dummy station). Afterwards you have to rebuild and download the programm of your first CPU, since the new IP-Table has to be downloaded to the station.
Categories
Communication / Ether-S-Bus
Last update: 25.05.2015 17:06
First release: 03.08.2005 11:35
Views: 1879