Can an xx7 series controller be both a Profibus-DP master and a DP slave?

FAQ #100087

Yes, this is possible with the PCD2.M177 and PCD2.M487. Please read the rules that must be respected in "Details".

 

With the PCD2.M177, a PCD7.F750 master module and PCD7.F770 slave module are required. Alternatively, with the PCD2.M487 the MPI interface can be used as Profibus-DP slave up to a maximum of 1.5 Mbit.

If you want to use a F750 module and a F770 module together on a PCD2.M177 then you have to use mandatory the F770 module on the slot B1 and the F750 module on the slot B2.

 

Categories

xx7 Series / Communication

Last update: 28.05.2015 12:31

First release: 08.06.2004 14:49

Views: 1166

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.