Wie löschen Sie gespeicherte Leistungsindikatorwerte in einem PCD7.H104S/SE
FAQ #101930
Zum Schreiben/den Wert des Indikators in der H104S/SE klar, muss die F-Box "H104S/SE-Set" verwendet werden.
The 'clear' input from the F-Box "H104S/SE read" does clear the stored counter values (which are stored in PCD register) but not the register in the H104S/SE.
If the PCD does read the next time the values from the H104S/SE, then the old values, stored in H104S/SE are copied again in the counter register of the PCD.
Therefore the 'clear' input of the F-Box "H104S/SE read" can not be used to clear the counter values in the H104S/SE.
To write (or clear) the counter value in the H104SE use the F-Box "H104S/SE Set".
Which register (addresses) must be written, can be found in the datasheet of H104S/SE.