Motor signals 1-stage@@&name@@
Logging of the prevalent motor failures, like operating feedback, rotary speed monitoring, motor protection, Rep.switch and manual control.
To prevent ghost signals in case of a fuse failure, a rejection of signal can take place depending on the associated voltage monitoring.
The collective error of the motor attached collective error always consists of the 3 standard signals 'operating feedback absent', 'motor protection activated' and 'process feedback absent'.
Alternatively, it can be also parameterised whether the signals Rep. switch and/or manual intervention should be likewise included in the collective error signal.
Parameter |
Value |
Operating feedback, delay |
@adj_BetriebVerzoeger.1p@ s |
Process feedback, normal status of the issuer (0=NO, 1=NC) |
@adj_ProzessNoNc.0p@ |
Process feedback, delay |
@adj_ProzessVerzoeger.1p@ s |
Motor protection, requiring acknowledgement (0=No, 1=Yes) |
@adj_MotorQuitTyp.0p@ |
Motor protection, normal status of the issuer (0=NO, 1=NC) |
@adj_MotorNoNc.0p@ |
Motor protection, rejection of failure in case of absent fuse (0=never, 1=always, 2=230 VAC, 3=24 VAC, 4=24 VDC, 5=phase monitor, 6=control voltage) |
@adj_MotorSpgGrp.0p@ |
Rep. switch, requiring acknowledgement (0=No, 1=Yes) |
@adj_RepSchalterQuitTyp.0p@ |
Rep. switch, normal status of the issuer (0=NO, 1=NC) |
@adj_RepSchalterNoNc.0p@ |
Rep. switch, rejection of failure in case of absent fuse (0=never, 1=always, 2=230 VAC, 3=24 VAC, 4=24 VDC, 5=phase monitor, 6=control voltage) |
@adj_RepSchalterSpgGrp.0p@ |
Manual intervention, normal status of the issuer (0=NO, 1=NC) |
@adj_HandeingriffNoNc.0p@ |
Manual intervention, rejection of failure in case of absent fuse (0=never, 1=always, 2=230 VAC, 3=24 VAC, 4=24 VDC, 5=phase monitor, 6=control voltage) |
@adj_HandeingriffSpgGrp.0p@ |
Collective error additionally includes (1=none, 2=Rep. switch, 3=manual intervention, 4=both) |
@adj_SsmTyp.0p@ |
Associated fuse monitoring |
@@&ref@@ |