Drive Open/Close @@&name@@
2-point drive (flap drive) with potential position feedback, enforced override, anti-block protection and manual override.
General functions
In case of an enforced override, how the drive should be controlled can be specified.
The drive can be provided with a turn-off delay. This is for instance required in flap drives with spring return, as they close faster than the fans run out.
An anti-block protection can be set. This controls the drive for the duration of the operating time with Open. The anti-block protection mechanism is centrally defined.
The feedback signals can be directly connected. If there are no position feedbacks available, this can be emulated through FBox (e.g. for the Start Ventilation FBox). The control is compared to the feedbacks. If the corresponding feedback is missing after the end of the operating time, an error signal is issued.
Parameter |
Value |
Building management system switch (1=Auto, 2=Close, 3=Open) |
@adj_HMI.0p@ |
Pre-selection for anti-block protection function (1=No, 2=Yes, 3=not available) |
@adj_Antiblock.0p@ |
Status in enforced override (0=Open, 1=Close) |
@adj_Zwangsbefehl.0p@ % |
Feedbacks (0=Emulate, 1=Available) |
@adj_RueckmeldungTyp.0p@ |
Rundown time |
@adj_Nachlauf.1p@ s |
Manual intervention of signal contact in normal status (0=NO, 1=NC) |
@adj_HandeingriffNoNc.0p@ |
Manual intervention, rejection of failure in case of absent fuse (0=never, 1=always, 2=230 VAC, 3=24 VAC, 4=24 VDC, 5=phase monitor, 6=control voltage) |
@adj_HandeingriffSpgGrp.0p@ |
Operating time |
@adj_Laufzeit.1p@ s |
Feedback monitoring requires acknowledgement (0=No, 1=Yes) |
@adj_RueckmeldungQuit.0p@ |
Feedback monitoring rejection of failure in case of absent fuse (0=never, 1=always, 2=230 VAC, 3=24 VAC, 4=24 VDC, 5=phase monitor, 6=control voltage) |
@adj_RueckmeldungSpgGrp.0p@ |