Diagnose Outputs for a Lon Device

Pre requisites

The Diagnostic screen displays:

Procedure

  1. Right click on the controller. Select Controller Diagnostics. The Diagnostics dialog box appears.
  2. Enter the value the sensor must detect in the Edit Value field and enter/select information as given in the following table.
Name Definition
Modulating Output The number of Modulating Outputs depends on the outputs configured in the application logic.

Actual Value: Displays the value of the modulating output read by the controller. This field is non-editable.

Edit Value: Enter the value that the sensor must be detecting. The range is 0-100 percent.

Binary Output The number of Binary Outputs depends on the outputs configured in the application logic.

Actual Value: Displays the value of the modulating output read by the controller. This                        field is non-editable.

Edit Value: Select True or False

Mode Displays the current mode of the device.
Set Click Set to set the controller to manual mode. It writes the configured values to the controller and automatically puts the modulating output in the manual mode.
Refresh Click Refresh to refresh the values.
Close Click Close to close the dialog box. It prompts you to set all inputs in the manual or auto mode.
  1. Click Close to close the dialog box.