SystemStatus Function Block
This parameter displays system status in the wall module.
|
Figure 2: SystemStatus Property Sheet |
Inputs
Input Name |
Description |
In |
To provide the system Status from the controller to the Wall module. |
Table 1: Inputs of SystemStatus Function
Output
Output Name |
Description |
NA |
|
Table 2: Output of SystemStatus Function
Parameters
Parameter Name |
Description |
Sylk Device |
Select the required TR7x or TR4x device from the drop-down menu. |
Status |
Read-only point. Shows the status of the parameter. (alarm, fault, overridden, disabled, down, stale, null, unackedAlarm). For further details see Sylk Component Status Behaviors. |
faultCause |
Read-only point. Indicates the reason why the parameter is in fault. This property is empty unless a fault exists. When there are more than one errors, the fault cause shows only the error which is at the top of the list of errors. If the error is corrected, the next error is shown. |
sendInterval Seconds |
Send interval is the time between the end of a timeout period or completion of a network request and the next request for data on the network. Default is 60 seconds. |
enableFD |
The time it takes for a failure to be reported to the Sylk device. "Yes": If the parameter has not received an update from the BACnet network source within the fail detect time, an alarm is generated, and the current value is set to invalid. Note: The time it takes to detect a failure is determined by the update rate that has been set. "No": No means that the object will retain the last value written to it until the BACnet network source changes. |
SyatemStatusValue |
Set the System Sate as per requirement. |
Table 3: Parameters of SystemStatus Function
Refer to General Description for general information about IRM N4 Function Blocks.