Index | Prev | Next
System Status Configuration
- Double-click SystemStatus on the wire sheet to configure the properties.

Figure 01: Property Sheet of SystemStatus
- sylkDevice: Select the required TR7x device from the drop-down menu

Figure 02: sylkDevice Drop-Down Menu
- Status: Read-only point. Shows the status of the parameter. (alarm, fault, overridden, disabled, down, stale, null, unackedAlarm). For further details see Sylk Component Status Behaviors.
- faultCause: Read-only point. Indicates the reason why the parameter is in fault. This property is empty unless a fault exists. When there are more than one errors, the fault cause shows only the error which is at the top of the list of errors. If the error is corrected, the next error is shown.
- pollInterval: Poll interval is the time between the end of a timeout period or completion of a network request, and the next request for data on the network
- EnableFD: Fail Detect is the time until the CIPer Model 30 is notified of a failure on this point.
- True: If the parameter has not received an update from the IPC network source in the fail detect time, then an alarm is generated and the presentValue is set to Invalid. Note that fail detect time depends on the update rate configured.
- False: False means the object retains the last value that was written to it until a IPC network source changes it or the Honeywell CIPer Model 30 has a power outage or reset.
- in: To provide the system Status from the controller to the Wall module.
- System Status Values: Set the System Sate as per requirement

Figure 03: Sub-Menu of systemStatusValues
- Click Save to save the changes made. Or click Refresh and then No, if you do not want to save the change
To add and configure SylkDevice, refer to SylkDevice Configuration.
Index | Prev | Next
Copyright © 2017-2018 Honeywell. All rights reserved.