Value From Wall Module Configuration
These are outputs from the wall module such as sensor values.
- Double-click ValueFromWallModule on the wire sheet to configure the properties.

Figure 01: Property Sheet of ValueFromWallModule
- numberOfDecimals: Provide the value of numbers of decimal as per requirement.
- incrementDecrement: Value of the setpoint to be increased or decreased at one step.
- defaultValue: Default value of the setpoint.
- limitConfig: To set the high and low limits of the setpoint.
If you provide the Low Limit From Sylk Param value, the value given in the Low Limit field is ignored.
If you provide the High Limit From Sylk Param value, the value given in the High Limit field is ignored.

Figure 06: Prpoerty Sheet of limitConfig
- Low Limit From Sylk Param: To select the Low limit value from the other Sylk parameter of the respective system device
- High Limit From Sylk Param: To select the High limit value from the other Sylk parameter of the respective system device
- Low Limit: Set the constant value for High limit
- High Limit: Set the constant value for Low limit
- selectLabelsToShowOnScreen: Select the required option (Setpoint top or Setpoint Bottom) to show the parameter on the home screen shown below:

Figure 07: Sub-Menu of selectLabelsToShowOnScreen

Figure 08: Display of Wall Module TR7X
- Click Save to save the changes made. Or click Refresh and then No, if you do not want to save the change
To add and configure SylkDevice, refer to SylkDevice Configuration.
Copyright © 2017-2018 Honeywell. All rights reserved.