Double-click SylkActuatorOutputParam on the wire sheet to configure the properties.
Figure 270: Property of SylkActuatorOutParam
sylkDevice: Select the required SylkActuator device from the drop-down menu.
Status: Read-only point, shows the status of the parameter. (alarm, fault, overridden, disabled, down, stale, null, unackedAlarm). For further details see Sylk Component Status Behaviors.
faultCause: Read-only point, displays the reason of the fault parameter. This property is empty unless a fault exists.
sendInterval (seconds): sendInterval is the time interval for sending output parameter value from Sylk device to the network periodically. Based on the user configured sendInterval the Sylk device will send the output parameter value to the controller.
Example: If sendInterval value set to 5 seconds then in every 5 seconds, the Sylk device will send output parameter value to the network.
Available interval range can be configured from 5 seconds to 75 seconds. The default sendInterval value is 5 seconds.
Note: |
|
If the Sylk device is configured at the higher address, then there is possibility that Sylk device will miss to write parameter periodic update on the network. It is recommended to set enableFD to “No.” (If enableFD is set to “Yes” there is chance, that the Sylk parameter value will be set to default if it fails to send parameter update which may impact its behavior.) Cov as sendInterval not supported when configuring for SylkActuatorOutputParam |
enableFD: Fail Detect is the time until the controller is notified of a failure on this point.
Yes: If enableFD set to “yes” then controller expects periodic update on Sylk output parameter. If it fails to receive parameter update from the Sylk device, then alarm will be generated and the Sylk output parameter value will be set to default value.
No: False means the parameter retains the last value that was written to it. It will not allow parameter value to be set to default value.
Out: Provides the respective value to the controller from the Sylk device.
outputType: This option allows you to configure Sylk Actuator output. SylkActuatorOutputParam can be configured in the following type of outputs:
Actuator Position: This is a feedback from the actuator’s current position ranging between 0 to 100 and can be mapped into the controller for monitoring.
Actuator Cycle Count: It shows how many time actuators is cycled from open to close position.
Actuator Status: Actuator status returns a number with the following meaning:
No Error
Under Voltage
Over Voltage
Stall
OverVoltage and Stall
UnderVoltage and Stall
Actuator Overridden: It provides actuator overridden status if actuator is overridden externally. This will return “True” if the unit is in Test Mode. This when the address pot is manually turned to position 6.
Power Report: This is a relative measurement. It is only calculated for the last commanded move, value ranging between 0 to 100.
Copyright © 2017-2018 Honeywell. All rights reserved.