SystemStatus Function Block

This parameter displays system status in the wall module.

Figure 1: SystemStatus Function Block

Figure 2: SystemStatus Property Sheet

Inputs

Input Name

Description

In

To provide the system Status from the controller to the Wall module.

Table 1: Inputs of SystemStatus Function

Output

Output Name

Description

NA

 

Table 2: Output of SystemStatus Function

Parameters

Parameter Name

Description

Sylk Device

Select the required TR7x or TR4x device from the drop-down menu.

Status

Read-only point. Shows the status of the parameter. (alarm, fault, overridden, disabled, down, stale, null, unackedAlarm). For further details see Sylk Component Status Behaviors.

faultCause

Read-only point. Indicates the reason why the parameter is in fault. This property is empty unless a fault exists. When there are more than one errors, the fault cause shows only the error which is at the top of the list of errors. If the error is corrected, the next error is shown.

sendInterval

Seconds

Send interval is the time between the end of a timeout period or completion of a network request and the next request for data on the network. Default is 60 seconds.

enableFD

The time it takes for a failure to be reported to the Sylk device.

"Yes": If the parameter has not received an update from the BACnet network source within the fail detect time, an alarm is generated, and the current value is set to invalid.

Note: The time it takes to detect a failure is determined by the update rate that has been set.

"No": No means that the object will retain the last value written to it until the BACnet network source changes.

SyatemStatusValue

Set the System Sate as per requirement.

Table 3: Parameters of SystemStatus Function

Refer to General Description for general information about IRM N4 Function Blocks.