Posso rilevare il segnale CTS sulla porta 3 di un PCD3.M5340 (in modalità RS422)?
FAQ #101170
Sì, questo è possibile con versione firmware 1.10.15 e successive.
With firmware version 1.10.15 and later, it is possible reading the CTS signal from port 3 in case RS422 is used on this port. The CTS signal can be read by executing the SICL instruction (it is also possible if the port is assigned and if the port is not assigned).
Additionally, it is possible writing the RTS and the COM signal using the SOCL instruction (again, only if RS422 is used).
Remark
Please note that the CTS does not exist on RS485 and therefore it can not be read, either.
Port | Type | Mode | Assigned (SASI) | SICL | SOCL | |||||||||
RS-232 | RS-422 | RS-485 | MC 0 | MC 1 | MC 2 | MC 4/5 |
| 0 | 1 DSR | 2 DCD | 0 RTS | 1 DTR | 2 COM | |
# 0 | - | - | - | No | - | - | - | |||||||
yes | - | |||||||||||||
# 1 | No | - | - | - | ||||||||||
yes | ||||||||||||||
# 2 | - | - |
| - | - | - | No | - | - | - | - | - | - | |
yes | - | - | - | - | - | - | ||||||||
# 3 | - | * | * | * | - | No | * | - | - | - | - | - | ||
yes | * | - | - | * | - | * | ||||||||
# 1xx | No | - | - | - | ||||||||||
yes |
*) HW dependant (only on PCD3.M5340)
Categories
PCD3 / Mxxx
Last update: 15.05.2015 13:34
First release: 24.03.2009 16:04
Views: 874