” after the function Network –>Test Reason In the FW 1.26.xx there is a problem with the file update on the Flash cards, the bindings are only updates in the memory but the [...] is processed (only this page is part of the current Fupla file! If the Error isn't caused by this Fupla file, it will jump to any other page which doesn't cause the problem. Have a look at this page [...] while beeing online with the next Fupla file of the CPU). If you can't find the problem directly in a Fupla file, switch to the Online Debugger again. After having stopped, a line similar to the line
range of 32. Therefore it is absolutely necessary to set the Base address to a multiple of 32. A Base address like e.g. 48 will cause problems [...] 5 Contols Suite). If a project was created with an older version of the programming tool, also the FB's provided with the older programming software were used. This may cause problems because of incompatibilities of the FB calls. To get around of this problem it is recommended to copy the used FBs directly into the CPU directory of the concerned project. This way the use of the correct FB version
range of 32. Therefore it is absolutely necessary to set the Base address to a multiple of 32. A Base address like e.g. 48 will cause problems [...] 5 Contols Suite). If a project was created with an older version of the programming tool, also the FB's provided with the older programming software were used. This may cause problems because of incompatibilities of the FB calls. To get around of this problem it is recommended to copy the used FBs directly into the CPU directory of the concerned project. This way the use of the correct FB version
If the cost calculation in the S-Monitoring is not correct, then do check the format of the PCD variables in the *.wvar file of the web-editor8. If for example the variable NT-EM,Addr,WTxtotal.Tariff does have a format definition, then the cost calculation doesn’t work correctly. To solve the problem remove the format definition in the format field and compile/download the project in to the PCD. It’s not allowed that the NT-EM… variables does have any format value in the format field.
Due of an error in PG5 2.1.430 the function ‘Add Files’ on the project manager, Program Files menu does crash the project manager as soon as a selected external file should be added to the project. Solutions: Either do not use the function ‘Add Files’ to add other files to the project but, copy/paste the files in to the project or extract the file Spm52.exe from the attached zip file and do copy/paste the file to the PG5 installation directory. c:\Program Files\SBC\PG5 V2.1.430\ New Spm52.exe has the version 2.1.430.4 old Spm52.exe which cause the problem is the version 2.1.430.0
In case alarming-texts are defined in a IL (*.src) or a Fupla file it is possible to display these alarming-texts on a VGA Panel, but specific char (as umlauts, swedish chars and others) do not appear correctly on the VGA Panel (which is equipped with FW 1.12.11).
When displaying a certain teq view, the MicroBrowser (MB Panel, CE Panel, iPhone & iPad App) stops working and displays the error message "file not found xxxx.teq" where 'xxxx.teq' is the name of the teq view from which the jump was executed. This problem occurs due to an invalid 'PLC-ID' inside a Macro used on the concerned teq view when compiled with a Web Editor 5.15.0200.
When having activated (or better said: not desactivated) the Syntax check of the FBoxes it is possible that errors as the following appear on build of the FBox library: Fatal Error 2312: C:\Documents and Settings\All Users\Saia-Burgess\PG5_20\.......\SPECIALI\SPECIALICheckSyn.SRC : Can't open $INCLUDE file xxxx.LIB
There are some problems with EDE files of a few manufacturers, because they are not in the right format.
If the PG5 (or the S-Bus driver SCommDdll) is already running and one doubleclicks a PG5 program file (such as *.src or *.fup), it is possible that the file is not opened but a window named SCommCom with the message "Try to load another SCommCom.dll..." is shown.