Motion control modules for servo drives for PCD3.M3xxx/..M5xxx/..M6xx0 Positioning module for 1 servomotor axis, encoder input 5 VDC/100 kHz, setpoint output ±10 V (12 bits) (connector type A included)
Also the Saia PCD® COSinus based PCD systems (PCD2.M480, PCD2.M5xx0, PCD3.Mxxx0) do feature 16383 registers, not all these registers can be accessed from systems which do only feature 4095 registers over S-Bus.
PCD3.M6860 with hardware revision < D: it's not possible to use a FW 1.25.xx or higher on this PCD Use the FW 1.24.59 on this PCD
When using a PCD7.F772 or PCD7.F802 on a PCD2.M1x7 with FW Version 3.110 only the RS 485 communication works. Otherwise the Profibus / LON communication did not work.
No, do not connect the RJ45 connector of a Ethernet Port of a PCD directly to Power over Ethernet (PoE). The RJ45 Ethernet port of the PCD will be destroyed if connected directly to PoE (Mode B) because our Ethernet port (PCD7.F655 or the integrated Ethernet ports on the PCD1.M0/M2, PCD2.M5 and PCD3 and all Panels with Ethernet ports) are not designed for this purpose.
Package does include the FW for the PCD1.M2, PCD2.M5, PCD3.M and the LonIP FW. This firmware does support the modules PCD7.W600 and PCD7.R610 Do use at least the PG5 firmware downloader version 2.1.311 or newer (included in PG5 patch 2.1.311 or newer) to prevent the loading of the FW 1.24.xx to a not compatible PCD.
Package does include the FW for the PCD1.M2, PCD2.M5, PCD3.M and the BACnet FW. This firmware does support the modules PCD7.W600 and PCD7.R610 Do use at least the PG5 firmware downloader version 2.1.311 or newer (included in PG5 patch 2.1.311 or newer) to prevent the loading of the FW 1.24.xx to a not compatible PCD.
The communication modules PCD2.F2150 and PCD3.F215 with BACnet MS/TP allow the direct connection of max. two BACnet MS/TP lines and can be plugged on a PCD1.M2, PCD2.M5 or PCD3. Furthermore [...] plugged into PCD I/O slot 0..3. Modules for the PCD1.M2 and PCD2.M5 PCD2.F2150 up to 255 devices Modules for PCD3.Mxxx0 PCD3.F215 up to 255 [...] .F221 Workaround to use the RS-232 S-Bus communication over converters: For the PCD3: Instead of using a PCD3.F221, use the PCD3.F121. For PCD1.M2 or PCD2.M5: Instead of using a PCD2.F2xx0, use the PCD
The communication modules PCD2.F2150 and PCD3.F215 with BACnet MS/TP allow the direct connection of max. two BACnet MS/TP lines and can be plugged on a PCD1.M2, PCD2.M5 or PCD3. Furthermore [...] plugged into PCD I/O slot 0..3. Modules for the PCD1.M2 and PCD2.M5 PCD2.F2150 up to 255 devices Modules for PCD3.Mxxx0 PCD3.F215 up to 255 [...] .F221 Workaround to use the RS-232 S-Bus communication over converters: For the PCD3: Instead of using a PCD3.F221, use the PCD3.F121. For PCD1.M2 or PCD2.M5: Instead of using a PCD2.F2xx0, use the PCD
Plug-in terminal blocks for the IEC-Controller PCD3.M6893 X1 – CAN bus terminal Plug-in spring terminal block, 3-pole, 0.14…1.5 mm2 (black block), labelled 0 to 2