. Web-Editor functions PCD3 Mxxx0 PCD2 M5xx0 PCD2 M480 PCD1.M135 PCD2.M1x0 PCS1 PCD3 Mxxx7 PCD2 M5xx7 PCD2.M487 PCD2.M1x7 Web Server 2 [...] PG5 1.4.300 the S-Web Editor together with an example, the required FBoxes and firmware versions for PCD2.M5xx0 and PCD3.Mxxx0 can be downloaded from the support site from section Software --> PG5 --> [...] Win_CE6.0_cf2GB_D515xTL_1.0.7.1 PCD7D5xxxTMxxx_CELERON: Image for eWin_CE5.0_cf128_D5xxxTM_%241.0.3.0 PCD7D5xxxTXxxx_XSCALE: Image for eWin_CE5.0_cf128_D5xxxTX_2.1.0.1 Booter update e
. Web-Editor functions PCD3 Mxxx0 PCD2 M5xx0 PCD2 M480 PCD1.M135 PCD2.M1x0 PCS1 PCD3 Mxxx7 PCD2 M5xx7 PCD2.M487 PCD2.M1x7 Web Server 2 [...] PG5 1.4.300 the S-Web Editor together with an example, the required FBoxes and firmware versions for PCD2.M5xx0 and PCD3.Mxxx0 can be downloaded from the support site from section Software --> PG5 --> [...] Win_CE6.0_cf2GB_D515xTL_1.0.7.1 PCD7D5xxxTMxxx_CELERON: Image for eWin_CE5.0_cf128_D5xxxTM_%241.0.3.0 PCD7D5xxxTXxxx_XSCALE: Image for eWin_CE5.0_cf128_D5xxxTX_2.1.0.1 Booter update e
The M-Bus communication between the "Hydrometer M-Bus Receiver 868" (alternatively called "MB-Receiver") and the PCD2.F2710 has been analyzed and it was found that the device does not conform to the M-Bus specification (SN EN 13757-2). Therefore it can not be used together with the PCD2/3.F27x(0).
The Profibus DP configurator of PG5 1.3 (older than SP1.3.120) does create configuration files that don't run on a PCD2.M110/120 equipped with FW 080 and older.
Yes, there are PCDs that support the transmission of EMails over an SMTP server if they are equipped with Ethernet interface. The PCD types that support this feature are: - PCD1.M1x5, PCD2.M150, PCD2.M170 and the PCD4.M170 equipped with PCD7.F650 or PCD7.F655. - PCD1.Mxxx0, PCD2.M5xx0, PCD3.Mxxx and PCD7.D4xxxT5F (with Ethernet option).
On the PCD1.M2, PCD3 and PCD2.M5 CPU's it's possible to change the TCP port number of the S-Web server by the use of the PG5 2.0 Device Configurator.
For parsing a PCD text for a specific expression (e.g. finding "world" in a PCD text with content "Hello world") a new System Function has been added for PCD3 and PCD2.M5xx0.
Yes, it is possible to connect one or two encoders with A, B and index signal directly to the onboard inputs of a PCD3.M2x30V6.
No, this function is only available on the PCD3.M5xxx.
Yes, it is possible to use the S-Net MPI port on the PCD3.M5xxx as free RS 485 port (S-Bus or Mode C per example).