If the S-Bus communication over TCP/IP between PCD’s does not work, then do check on the TCP/IP settings table of the PG5 project manager that the field “use” is checked for each line (device) which have to communicate over S-Bus TCP/IP. It’s possible that after an import of a PG5 1.4 project in to PG5 2.0 the field “use” on the TCP/IP settings table is unchecked and therefore the communication over S-Bus TCP/IP doesn’t work.
On the patch 1 of the PG5 2.0.220 there is a error which does lead to the situation, that data’s which are defined by the user as ‘data transfer array’ where no more exchanged between the PCD3.T66x and the smart automation manager. This error occures during compilation of the project, but doesn't corrupt the original project. The configured I/O’s of the PCD3.T66x are exchanged without problems between the devices. The patch 2 for PG5 2.0.220 will fix this error and will be available soon.
Due of an error on the FW the overflow status flag of the onboard analogue inputs does not work correctly. This flag was set to high in the middle of the measurement range and not if the maximum valu
PCD6.E100, PCD6.E610, PCD6.E611 or PCD6.A350 (FAQ #100264) These 4 digital I/O cards have all an address [...] . Nevertheless it is possible measuring the range 0..20 mA with the analogue input modules for PCD systems. Why do the SBC input modules have a range of 0..20 mA? One advantage of measuring the [...] the used power supply does not have the +/-15V the analogic carts can not work. With the PCD4/6.N200 supply it is not possible to use analogic cards. You will need the PCD4/6.N210 supply
PCD6.E100, PCD6.E610, PCD6.E611 or PCD6.A350 (FAQ #100264) These 4 digital I/O cards have all an address [...] . Nevertheless it is possible measuring the range 0..20 mA with the analogue input modules for PCD systems. Why do the SBC input modules have a range of 0..20 mA? One advantage of measuring the [...] the used power supply does not have the +/-15V the analogic carts can not work. With the PCD4/6.N200 supply it is not possible to use analogic cards. You will need the PCD4/6.N210 supply
MC5 mode on F2xxx module All PCD’s: RS485 driver keep holding bus after a while All PCD’s: Http request ‘is modified’ is not handled correctly on the PCD Web-Server which lead to the effect that [...] (CVE-2017-9628) All PCD's: The Modbus CSF CloseSRPort does not free the port then a open/SASI call give an error and the port does not work. PCD1.M2xx0 PCD1.M22x0 PCD2.M4x60: PCD can crash while power down [...] SRPort does not free the port then a open/SASI call give an error and the port does not work. PCD1.M2xx0 PCD1.M22x0 PCD2.M4x60: PCD can crash while power down when XOB 0 is programmed. PCD1.M2xx0 PCD
The chapters of the documents below will introduce the reader into the main handling and programming of a Saia PCD® Classic. This introduction will allow a technician to realize an easy application. Hardware overview Installation of hardware Connecting a PCD to a PC and configuring the hardware Programming the first application Refer to [...] PCD to a PC and configuring the hardware Process image of a Saia® Classic PCD Overview over PCD resources Programming philosophies PG