PCD6.E100, PCD6.E610, PCD6.E611 or PCD6.A350 (FAQ #100264) These 4 digital I/O cards have all an address [...] . Nevertheless it is possible measuring the range 0..20 mA with the analogue input modules for PCD systems. Why do the SBC input modules have a range of 0..20 mA? One advantage of measuring the [...] the used power supply does not have the +/-15V the analogic carts can not work. With the PCD4/6.N200 supply it is not possible to use analogic cards. You will need the PCD4/6.N210 supply
version 005 can be found on the PCD4.M1x0 pages. PCD4.M340 (obsolete): CPU0 has got the same firmware as a PCD4.M1x0, the latest version 005 can be found on the PCD4.M1x0 pages. CPU1 with LAN2 has the [...] (or in case a PC is used, by interpreting the tracewin files). This phenomenon can be observed on PCD1.M1x5, PCD2.M150, PCD2/4.M170 and PCS1 systems (with firmware which are supporting the "Secure S [...] appears if the used firmware on the CPU does not support the "active and non ACK" filter for the S-Web alarming functionality (e.g. a PCD2.M150 with firmware 0D3). Symptom Instead of the
supply voltage pins 1L/2L and 3N/4N are inverted. This wrong label is present on the schema of the housing and directly on the pins. Problem When a PCD7.T162 produced before week 22 of 2011 (30.05.2011) has a 24V DC supply voltage it does not work when it is connected like described in the schema on the housing. Solution The pins 1L/2L and 3N/4N are printed inversely. This means that the functionality is still the same but the 24V DC need to be connected to the pins 3N/4N and the 0V to 1L/2L. Remark Units of PCD7.T162 produced after 11/22 (30.05.2011) are correctly labelled and
Fupla Good to know The FBox library version 2.6.176 for the ALD/ALE/AWD with Serial-S-Bus can be "grouped by function" in the FBox selector window of PG5 2.0.200. The Energy meter with Serial-S-Bus FBox library version 2.x.171 contains a new SASI FBox explained in FAQ 101469 . The Energy meter with Serial-S-Bus FBox library version 2.x.156 contains a correction explained in FAQ 101443 . The Energy meter with Serial-S-Bus FBox library version 2.x.155 contains a correction explained in FAQ 101432 .
Good to know The FBox library version 2.6.176 for the ALD/ALE/AWD with Serial-S-Bus can be "grouped by function" in the FBox selector window of PG5 2.0.200. The Energy meter with Serial-S-Bus FBox library version 2.x.171 contains a new SASI FBox explained in FAQ 101469 . The Energy meter with Serial-S-Bus FBox library version 2.x.156 contains a correction explained in FAQ 101443 . The Energy meter with Serial-S-Bus FBox library version 2.x.155 contains a correction explained in FAQ 101432 .
Certificates MID Certificates can be found in the certificates section Good to know The FBox library version 2.6.176 for the ALD/ALE/AWD with Serial-S-Bus can be "grouped by function" in the FBox selector window of PG5 2.0.200. The Energy meter with Serial-S-Bus FBox library version 2.x.171 contains a new SASI FBox explained in FAQ 101469 .
Procedure for updating the firmware of a PCD2.F2xx0 or PCD3.F2xx
Procedure for updating the firmware of a PCD2.F2610 or PCD3.F261
It's possible to update a PG5 project which include also Graftec files from PG5 2.1.210 to PG5 2.1.310 and compile and download the project in to the PCD. But after making some changes in the Graftec project it's no more possible to compile any more the project and all symbol definitions in Graftec are lost.
Due of an error on PG5 2.1.210, then IP-Node information is not stored correctly on the application program. This could lead to the situations that after a program download with PG5 2.1.210 the Ether-S-Bus communication doesn’t work anymore between some stations. To solve the problem, copy the attached file Spm52.exe (version 2.1.210.1 or higher) to the PG5 2.1.210 installation folder, compile again the concerned CPU and do load the concerned CPU to the PCD. This version will be included also in the next patch for PG5 2.1.210