No. This cable is not designed for connecting a PCD2.Cxxx extension housing. Connecting a PCD2.Cxxx can damage the involved hardware.
No, the PCD2.M5 CPU supports only one TCP/IP address. The two Ethernet connectors ETH1 and ETH2 do act as a switch.
No, do not connect the RJ45 connector of a Ethernet Port of a PCD directly to Power over Ethernet (PoE). The RJ45 Ethernet port of the PCD will be destroyed if connected directly to PoE (Mode B) because our Ethernet port (PCD7.F655 or the integrated Ethernet ports on the PCD1.M0/M2, PCD2.M5 and PCD3 and all Panels with Ethernet ports) are not designed for this purpose.
No, it’s only possible to connect an NTC10kOhm temperature sensor to the S or E2 terminal. If a PT1000 temperature sensor is connected to the S terminal of a PCD7.L60x room controller, then all the time the temperature value will be used/shown, which is defined as “temperature via SBus” in the “HVC Room” F-Box of the F-Box family ‘RoomController PCD7_L60x SV2_11/13’
Yes, the PCD7.W600 analogue input module is supported on the PCD2.M4x60 since the hardware version C of the PCD2.M4x60.
Product Category Programmable controller PCD2: CPUs, flat design Kxxx: Cables and terminals K1xx General FAQ PCD2.A3xx Digital output modules (2 A
Product Index PCD2 Kxxx: Cables and terminals K1xx General FAQ PCD2.A3xx Digital output modules (2 A
#100589) Years ago a commissioning tool for some motion modules (e.g. PCD2.H32x) has been developped and was set to the beta [...] . Remark Please note that in case the option "Full RS-232 handshaking on Port 0" (for modem connections) is checked in the hardware settings of a PCD3.M5 or a PCD2.M5, the PGU signal (DSR) can no longer [...] 8.K100 (for PCD8.P100) and .K110 (for PC's) are obsolete and replaced by PCD8.K101 and .K111 respectively. The new cables support as well the S-Bus protocol and are required to program PCD1.Mxxx, PCD2.M150, PCD2
4.M340 (obsolete): CPU0 has got the same firmware as a PCD4.M1x0, the latest version 005 can be found on the PCD4.M1x0 pages. CPU1 with LAN2 has the same firmware as a PCD6.T1xx, last version 005, only available on [...] (or in case a PC is used, by interpreting the tracewin files). This phenomenon can be observed on PCD1.M1x5, PCD2.M150, PCD2/4.M170 and PCS1 systems (with firmware which are supporting the "Secure S [...] appears if the used firmware on the CPU does not support the "active and non ACK" filter for the S-Web alarming functionality (e.g. a PCD2.M150 with firmware 0D3). Symptom Instead of the
Product Category Programmable controller PCD2: CPUs, flat design Kxxx: Cables and terminals K2xx General FAQ PCD2.A3xx Digital output modules (2 A