inputs of a module PCD2/3.W525 could perturbate an other input of the same module Module PCD2/3.W525 are not designed as other analog input modules (as PCD2/3.W340 or W200 for example). Particularities [...] correctly. Solution This problem is solved with hardware version A or C and newer of the PCD2.W6x5 or PCD3.W6x5 respectively. What is the signification of the I/O words of a PCD2/3.W525 module? (FAQ #101552) When configuring a W525 module using
address 240). On all other slots the modules work correctly. Solution This problem is solved with hardware version A or C and newer of the PCD2.W6x5 or PCD3.W6x5 respectively [...] PCD2.W745 is used on a PCD3.T760 RIO module 6 registers are available on the master station. It is important to know that the 2 first registers contain the diagnostic bits of the 4 inputs channels [...] : There's an error in allocating the address mapping of the Device Configurator in PG5 2.0.200 (SP2) for this analog card PCD3.W745. Solution: This problem will be solved in PG5.2
inputs of a module PCD2/3.W525 could perturbate an other input of the same module Module PCD2/3.W525 are not designed as other analog input modules (as PCD2/3.W340 or W200 for example). Particularities [...] correctly. Solution This problem is solved with hardware version A or C and newer of the PCD2.W6x5 or PCD3.W6x5 respectively. What is the signification of the I/O words of a PCD2/3.W525 module? (FAQ #101552) When configuring a W525 module using
Product Category Programmable controller PCD2: CPUs, flat design Wxxx: Analogue I/O W4xx General FAQ PCD2.A3xx Digital output modules (2 A
inputs of a module PCD2/3.W525 could perturbate an other input of the same module Module PCD2/3.W525 are not designed as other analog input modules (as PCD2/3.W340 or W200 for example). Particularities [...] connected with a wire as short and thick as possible to pin 22/23 (for PCD1) or pin 23/24 (for PCD2) respectively [...] 'freeze' during a time of about 1 to 2 minutes. Afterwards, the modules function again and the measured analog input value is updated again in the application program. Affected modules: PCD
. PCD3 / Wxxx On a PCD2.M4560 or PCD3.M5560, why [...] If the PCD2/3.W220Z18 card is plugged in to a ‘Power PCD‘ or a PCD2.C1000 or PCD2.C2000 and if all 8 analog inputs channels of the PCD2/3.W220Z18 module are connected to 8 PT100 sensors then the [...] 3.Mxx60 To solve the issue, use and connect only up to 7 PT100 sensors to the PCD2/3.W220Z18 or do use a PCD2/3.W350 module, if all 8 PT100 are needed. On the ‘old’ PCD’s like PCD2.M170 or PCD3.M5540 the
. PCD3 / Wxxx On a PCD2.M4560 or PCD3.M5560, why [...] If the PCD2/3.W220Z18 card is plugged in to a ‘Power PCD‘ or a PCD2.C1000 or PCD2.C2000 and if all 8 analog inputs channels of the PCD2/3.W220Z18 module are connected to 8 PT100 sensors then the [...] 3.Mxx60 To solve the issue, use and connect only up to 7 PT100 sensors to the PCD2/3.W220Z18 or do use a PCD2/3.W350 module, if all 8 PT100 are needed. On the ‘old’ PCD’s like PCD2.M170 or PCD3.M5540 the
inputs of a module PCD2/3.W525 could perturbate an other input of the same module Module PCD2/3.W525 are not designed as other analog input modules (as PCD2/3.W340 or W200 for example). Particularities [...] connected with a wire as short and thick as possible to pin 22/23 (for PCD1) or pin 23/24 (for PCD2) respectively [...] 'freeze' during a time of about 1 to 2 minutes. Afterwards, the modules function again and the measured analog input value is updated again in the application program. Affected modules: PCD
version 005 can be found on the PCD4.M1x0 pages. PCD4.M340 (obsolete): CPU0 has got the same firmware as a PCD4.M1x0, the latest version 005 can be found on the PCD4.M1x0 pages. CPU1 with LAN2 has the [...] (or in case a PC is used, by interpreting the tracewin files). This phenomenon can be observed on PCD1.M1x5, PCD2.M150, PCD2/4.M170 and PCS1 systems (with firmware which are supporting the "Secure S [...] appears if the used firmware on the CPU does not support the "active and non ACK" filter for the S-Web alarming functionality (e.g. a PCD2.M150 with firmware 0D3). Symptom Instead of the
4.M340 (obsolete): CPU0 has got the same firmware as a PCD4.M1x0, the latest version 005 can be found on the PCD4.M1x0 pages. CPU1 with LAN2 has the same firmware as a PCD6.T1xx, last version 005, only available on [...] (or in case a PC is used, by interpreting the tracewin files). This phenomenon can be observed on PCD1.M1x5, PCD2.M150, PCD2/4.M170 and PCS1 systems (with firmware which are supporting the "Secure S [...] appears if the used firmware on the CPU does not support the "active and non ACK" filter for the S-Web alarming functionality (e.g. a PCD2.M150 with firmware 0D3). Symptom Instead of the