Why on PG5 2.3.192, the error message ‘Error 1279: xxx.fbd: Line 278: String name not defined’ is displayed after compilation of a Fupla project containing ‘Alarm advanced’ FBoxes?

FAQ #102048

If the Fupla project contains ‘Alarm advanced’ FBoxes then since PG5 2.3.192 it’s mandatory to place a ‘Plant Code’ FBox on the Fupla project.

The ‘plant code’ FBox must be placed before the first ‘Alarm advanced’ FBox.

On older PG5 version the ‘Plant Code’ FBox was not mandatory.

 

More information can be found on the attached document.

 