Why do measured input values for PCD2.W3x5 / PCD3.W3x5 cards "freeze"
FAQ #102043
It can occur that the value measured from the PCD2.W3x5 / PCD3.W3x5 modules 'freeze' during a time of about 1 to 2 minutes.
Afterwards, the modules function again and the measured analog input value is updated again in the application program.
Affected modules:
PCD3.W3x5 cards manufactured between 1801 and 1916. (FW 1.04.00 or FW 1.04.02)
The manufacturing date is marked on the white sticker on the right side of the module.
Symptoms:
The measured value of the PCD2.W3x5 / PCD3.W3x5 cards can freeze freezes for 1 or 2 minutes. The measured value stays on the same value, there is no change. This will occur on average 1-3 times during 3 hours. This is due to a malfunction of the firmware of the module.
Afterwards, the modules function again and the measured analog input value is updated again in the application program.
Solution:
There is no isse for 'standard' HEVAC applications where no fast reaction time (< 2 minutes) is required.
For critical applications where this malfunction is not acceptable, we recommend the exchange of the affected PCD2.W3x5 / PCD3.W3x5 modules with new modules (manufacturing date 1916 or newer)
To replace the affected modules:
Order new PCD2.W3x5 / PCD3.W3x5 modules from SBC and send the affected modules back to SBC via RMA.
In the RMA form, note 'Advance exchange' with the remark '8D-SBC-19-001' in the comment.
The affected PCD2.W3x5 / PCD3.W3x5 modules will then be credited to you.