Why after the change of a PCD6.R210 memory support module in a PCD6 installation, the program does no more work correctly in the PCD6?

FAQ #101923

The PCD6.R210 module is a support module for the PCD6.R600 memory module.

 

The PCD6.R600 does contain the PCD program but does not contain the S-Bus station number of the PCD.

 

Therefore if the PCD6.R600 module is put in to a new PCD6.R210 module, it’s necessary to write with PG3/PG4 or PG5 the S-Bus station number to the PCD6.R210 module.

 

 