The actual IP adress, subnet-mask or gateway configuration is modified after a save / boot of the WinCE Panel.

FAQ #101887

There is a error in the WebPanel configurator 1.7 for CE web-panels (this version is installed with the image eWin_CE6.0_cf128_D510xTL_1.0.7.0)

which does lead to the situation that the configured TCP/IP settings of the CE panel does change after a save / reboot of the panel.

 

For example, the configuration was modified like this:

 before reboot
after reboot
IP-Adress 172.20.10.90
172.20.10.90
Subnet-Mask 255.255.255.0
255.255.255.0
Gateway
172.20.10.1 
 0.0.0.0
DNS1
0.0.0.0  
0.0.0.0  
DNS2
0.0.0.0  
0.0.0.0  
Lan 2, Fix IP
  
IP-Adress 
172.20.10.90
172.20.10.90 
Subnet-Mask
255.255.255.0
172.20.10.90
Gateway
0.0.0.0   
0.0.0.0   
DNS1 
0.0.0.0   
0.0.0.0   
DNS2
0.0.0.0   
0.0.0.0   












Cause:
There a bug in the Web Panel Configurator 1.7

Solution:
Unzipp and copy the attached file (Web Configurator 1.5) and do replace the actual version on:
\StorageCard\WebPanel_PowerToys
Or use an older image version as the version 1.0.7.0 (available form support web site)
for example the version eWin_CE6.0_cf128_D510xTL_1.0.6.9

 

Related Files:

Categories

PCD7 / D5xxx (Windows CE)

Last update: 01.06.2015 01:22

First release: 27.02.2014 15:11

Views: 165

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.