The actual IP adress, subnet-mask or gateway configuration is modified after a save / boot of the WinCE Panel.
FAQ #101887
There is a error in the WebPanel configurator 1.7 for CE web-panels (this version is installed with the image eWin_CE6.0_cf128_D510xTL_1.0.7.0)
which does lead to the situation that the configured TCP/IP settings of the CE panel does change after a save / reboot of the panel.
For example, the configuration was modified like this:
before reboot | after reboot | |
IP-Adress | 172.20.10.90 | 172.20.10.90 |
Subnet-Mask | 255.255.255.0 | 255.255.255.0 |
Gateway | 172.20.10.1 | 0.0.0.0 |
DNS1 | 0.0.0.0 | 0.0.0.0 |
DNS2 | 0.0.0.0 | 0.0.0.0 |
Lan 2, Fix IP | ||
IP-Adress | 172.20.10.90 | 172.20.10.90 |
Subnet-Mask | 255.255.255.0 | 172.20.10.90 |
Gateway | 0.0.0.0 | 0.0.0.0 |
DNS1 | 0.0.0.0 | 0.0.0.0 |
DNS2 | 0.0.0.0 | 0.0.0.0 |
Cause:
There a bug in the Web Panel Configurator 1.7
Solution:
Unzipp and copy the attached file (Web Configurator 1.5) and do replace the actual version on:
\StorageCard\WebPanel_PowerToys
Or use an older image version as the version 1.0.7.0 (available form support web site)
for example the version eWin_CE6.0_cf128_D510xTL_1.0.6.9
Categories
PCD7 / D5xxx (Windows CE)
Last update: 01.06.2015 01:22
First release: 27.02.2014 15:11
Views: 144