With PG5 2.1.100, why do I get the error "LONIP FAIL 1007"
FAQ #101831
Problem
After compiling and download of a LON IP project with PG5 2.1.100.0, the error LONIP FAILED 1007 is shown in the history of the PCD and the PCD goes to halt.
This problem is due to a bug in the LONIP configurator of PG5 2.1.100.
With PG5 2.0.220.200 this problem was not yet present.
Solution
Install the patch 1 for PG5 2.1 that can be downloaded from the Support homepage in the section Software / PG5 2.1 Suite.
Categories
PG5 2.0 / LON on IP
PG5 2.1
Last update: 21.05.2015 01:16
First release: 30.05.2013 06:19
Views: 3281