Problem on PG5 2.0 device configurator concerning the W745 module and Media mapping on PCD1M2120.

FAQ #101818

There is a problem on PG5 2.0 device configurator concerning the W745 module and Media mapping on PCD1M2120. The error message:

Error 2021: _Device2.obj: Unresolved external symbol: S.IO.Slot0.StatusAnalogueInput

appears after compiling.

 

 

There is a problem concerning the W745 module and Media mapping on PCD1.M2120. 

If a W745 module is inserted in device configurator of PG5 2.0, media mapping is enabled and then we use a symbol name relative  for example AnalogueInput0 with address S.IO.Slot0.AnalogueInput + 0 in fupla file the error message:
Error 2021: _Device2.obj: Unresolved external symbol: S.IO.Slot0.StatusAnalogueInput
appears after compiling.

This error is present in version PG5 2.0.200 and it has been fixed for the next version PG5 2.1.100.
If you need to fix this in version 2.0 what you have to do is the following :

Replace the file pcd2analogio_w4-9xx,  in the PG5 2.0 Installation:

C:\Program Files\SAIA-Burgess\PG5_20\DeviceTemplates then Remove the W.745 Module, and reinsert it again.



The file pcd2analogio_w4-9xx is attached in this FAQ:


 

Categories

PG5 2.0 / Device Configurator

Last update: 27.05.2015 21:56

First release: 25.02.2013 14:01

Views: 2923

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download