Why the S-Bus communication over TCP/IP between PCD’s doesn’t work anymore?

FAQ #101679

If the S-Bus communication over TCP/IP between PCD’s does not work, then do check on the TCP/IP settings table of the PG5 project manager that the field “use” is checked for each line (device) which have to communicate over S-Bus TCP/IP.

It’s possible that after an import of a PG5 1.4 project in to PG5 2.0 the field “use” on the TCP/IP settings table is unchecked and therefore the communication over S-Bus TCP/IP doesn’t work.

 

 