Why the S-Bus communication over TCP/IP between PCD’s doesn’t work anymore?

FAQ #101679

If the S-Bus communication over TCP/IP between PCD’s does not work, then do check on the TCP/IP settings table of the PG5 project manager that the field “use” is checked for each line (device) which have to communicate over S-Bus TCP/IP.

It’s possible that after an import of a PG5 1.4 project in to PG5 2.0 the field “use” on the TCP/IP settings table is unchecked and therefore the communication over S-Bus TCP/IP doesn’t work.

 

 

Categories

PG5 2.0 / PG5

Communication / Ether-S-Bus

PG5 2.0 / Fupla

PG5 2.0 / Project Manager

Last update: 01.06.2015 09:03

First release: 27.09.2011 14:43

Views: 30031

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download