Why is it no longer possible to switch on/off the digital outputs of the PCD3.Compact after installing PG5 SP2 (PG5 2.0.200)?
FAQ #101663
Due to an error in the PG5 device template file of PG5 2.0.200 it’s not possible to switch on/off the digital outputs of the PCD3.compact CPUs. (PCD3.M2030V6, PCD3.M2130V6)
Problem
Due to an error in the PG5 device template file of PG5 2.0.200 it’s not possible to switch on/off the digital outputs of the PCD3.compact CPUs. (PCD3.M2030V6, PCD3.M2130V6)
Solution
Either use a version of PG5 2.0 more recent than 2.0.200 or copy the attached file "pcd3compactfamily.saiaxml" into the folder:
c:\Program Files\SAIA-Burgess\PG5_20\DeviceTemplates\ and restart PG5 2.0.
Categories
PCD3 / Mxxx
Last update: 25.05.2015 07:36
First release: 19.08.2011 08:24
Views: 6136