On PG5 2.0 the error message „No _global.sy5 file found in the PG5 project” is shown after opening the HMI editor.

FAQ #101661

The HMI editor does point to the file _global.sy5 which does contain the PCD resources.

This file _global.sy5 is created each time that the program is build or if the HMI editor is open.

If the file _global.sy5 does not exist, then the error message shown above is displayed.

 

To force the creation of the _global.sy5 file when the HMI editor is open the following PG5 2.0 options have to be set as following:

 

On the menu point “Tools, Options, Build”

 

Background Build: Yes

Stop build on first error: No

 

 

Categories

PG5 2.0 / HMI Editor

Last update: 27.05.2015 06:10

First release: 18.08.2011 14:43

Views: 17961