Why does the DDC Suite S-Web add-on from PG5 2.0 SP2 not check for multi-defined alarms?
FAQ #101650
The add-on tool for S-Web Alarms of the DDC-Suite (included in PG 5 2.0.200) does not check for multi-defined alarms.
Symptom
The add-on tool for S-Web Alarms of the DDC-Suite (included in PG 5 2.0.200) does not check for multi-defined alarms.
Reason
There is a bug in the new SWebAlarm add-on tool of the DDC- Suite (which is included in PG 5 2.0.200). The previous version of the tool has always checked if an alarm number was defined more than once, in this case a warning message appeared. Now this check is ignored, and the csv is generated independently whether there is multi-defined alarm numbers or not.
Solution
Please update your PG5 2.0 to version 2.0.210 which corrects will generate an alarm in such a situation.