Why are the values not displayed on the webpage when connecting over modem with Webconnect

FAQ #101430

If a webconnection is established over modem with the current Webconnect 2.0.18.2 the webpages is displayed, otherwise the values are missing.

 

Problem
If all files except the .tcr file are stored in C:\Webpages the values are not displayed when connecting over modem. It is always necessary to execute a reload.

Reason
The reason is, that if the htm or html file is stored local in C:\Webpages the webconnect does not establish the connection with the PCD imediatly, since all necessary data is available offline.

Solution
To solve this problem the htm or html file has to be downloaded to the PCD using the Webbuilder (.wsp).

Additional information:
All files that are stored in C:\Webpages has to be stored in a subfolder with the name of the connection.

 

Categories

WebConnect

Last update: 28.05.2015 04:18

First release: 27.05.2010 15:11

Views: 3158

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.