How long does the SuperCap of the PCD3.M3xxx protect the media and RTC from being lost?

FAQ #101426

The resources (registers, flags, timers, counters etc) and possibly the user program and the text strings/DBs on a PCD3.M3xx0 are stored in RAM. To ensure that they are not lost and that the hardware clock (where present) continues to run when there is a power failure, the PCD3s are equipped with a buffer capacitor (SuperCap).

Unfortunately the time has not been specified correctly in the manual 26/789 until version 11 of the manual. The duration is 4 hours and not 8 hours (after the SuperCap has been charged while 10 minutes).

 

 

Categories

PCD3 / Mxxx

Last update: 25.05.2015 07:15

First release: 12.05.2010 14:59

Views: 6204

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download