Why is the message "Loading Data" continously displayed by the "RemoteOffSavedTrd....._5_14_25.esm" macro?

FAQ #101419

In case the image version (eWin_CE5.0_cf128_D5xxxTX_2.0.31.1.esy) of the CE_Panel (PCD7.D5xxxTX) is used, data seem to be continously loaded but not displayed (when using the macro for the "HDLog to File" FBoxes).

 

Symptom
In case the image version (eWin_CE5.0_cf128_D5xxxTX_2.0.31.1.esy) of the CE_Panel (PCD7.D5xxxTX) is used, it seems as if the panel is continously loading data but nothing is displayed.

Reason
According to FAQ 101273 (link below) the "HDLog trending to PCD File System" functionality on the CE Panel requires a MicroBrowser version higher than 1.5.14.105.
In the last Image Version (eWin_CE5.0_cf128_D5xxxTX_2.0.31.1.esy) of the PCD7.D5xxxTX, the version of the Microbrowser is the version 1.5.14.103 
This version of the MicroBrowser is not adadpted to run with the "HD Log trending to PCD File System" functionnalites.


Solution
Please updated the Microbrowser:

  • Please download the attached update file "Micro-Browser_PCD7D5xxxTX_1.5.14.109.cab" and move it on the CE Panel on the path /StorageCard/Micro-Browser/
  • Make a double click on this File and you will have to click 2 times "OK"
  • Then check if you have the version 1.5.14.109 of the MicroBrowser