Why is it not possible to choose minimal and maximal value in the device configurator for the PCD3 compact?
FAQ #101311
Instead of the maximal value it is just possible to set the minimal value twice.
Problem
In the Device configurator for PG5 1.4 it is not possible to configure the minimal and maximal value for the PCD3 compact (only in case the Device Configurator is used in German language):
§ix101048§
Only the minimal value is availabe, but twice.
Reason
This is a bug in the Device configurator (concerns only the German language version of the Device Configurator).
Solution
Please install patch 11 (or later) for PG5 1.4.300 in order to solve this problem. This patch is availabe on the support site in the PG5 1.4.300 section.