Why can I only read but not send EIB telegrams?

FAQ #101207

When working with a Siemens 5WG1 148-AB04 connected on e.g. a PCD3.F121 module, the following points need to be considered for successful operation.

 

Symptom
In the above mentioned constellation EIB telegrams are received but the transmission of EIB telegrams is not working.

Reason
This phenomenon can be caused by either an incorrect wiring or if the EIB group address of the BCU unit (coupler) doesn't fit.

Solution
Make sure that

  • the EIB address of the BCU unit fits the EIB network
  • the DTR/DSR lines are connected as in the wiring shown below 

Wiring of PCD3.F121 to BCU FT1.2
§ix101119§

 

Categories

Communication / EIB

Last update: 21.05.2015 11:10

First release: 08.05.2009 09:22

Views: 3474

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.