Is parity mode working on all ports of PCD3 and PCD2.M5 CPU?

FAQ #101103

There have been some restrictions concerning the usage of the S-Bus parity mode as master (SM1) on the PCD3.M and PCD2.M5 CPU. Since firmware version 1.10.51 these restrictions are eliminated.

 

The port 0 and 3 didn't support parity mode as Master between FW version 010 and 1.10.51 (while at this time all other ports supported the S-Bus Parity mode as master).
Since firmware version 1.10.51 it is possible to use the port 0 and 3 as Master in parity mode (all ports support parity mode as master and slave).

 

Categories

PCD3 / Mxxx

PG5 2.0 / Serial-S-Bus

PCD2 / M5xxx

Last update: 21.05.2015 00:53

First release: 14.01.2009 13:42

Views: 40848

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.