Why the action of the Web Editor "Set Var on Mouse DOWN / UP" does not work on a Panel eXP?
FAQ #101092
The action "Set Var on Mouse DOWN / UP" does not work correctly when you display a web project on a eXP (PCD7.D6..) panel.
Symptom
The value of the item behind the action "Set Var on Mouse DOWN" is automatically put back to the value 0 after a few seconds even if you are still touching the screen of the Panel eXP.
Reason
This behaviour is due to the feature "right click" of the touch screen on the eXP panel.
Solution
This problem can be solved if you disable the option "Enable right click emulation" in the settings of the Control Panel.
Path: Start -> Hampshire TSHARC Control Panel -> Click Settings
or Start -> Programme -> Hampshire TSHARC Control Panel -> Click Settings
Categories
PCD7 / D6xxx (Windows eXP)
Last update: 28.05.2015 21:29
First release: 17.12.2008 15:44
Views: 2509