Why it's not possible to access to the file system of a PCD7.D457VTCF and PCD7.D457VMCF TFT VGA MB Panel?

FAQ #101087

Sometimes it's not possible to access to M1_flash or to M1_flash/webpages of the PCD7.D457VTCF and PCD7.D457VMCF with FTP connection. (With FW 0.10 or 0.20)

 

Solution:
Download the new firmware V 1.00.00 or more recent, then format the M1_flash (by using the setup menu command "Format M1_flash").
Wait for about 2 minutes and after the message "format ok" switch off and on the panel.
Now it's possible to copy files to the folder M1_flash/webpages.
If you have problems to download the FW V1.00.00, then see the FAQ #101088

 

Categories

PCD7 / D4xx (MB Panel)

Last update: 01.06.2015 04:06

First release: 11.12.2008 12:29

Views: 1413

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download