Why it's not possible to use the whole memory of a file system on flash?

FAQ #101082

When i use for example a PCD3 Compact with 1MB Flash File-System (INTFLASH), the FTP-Client stops downloading data after max. 900kB.

 

There are more or less 100kB of the File-System memory reserved by the PCD system (64kB are reserved for the File-Compression feature and also some more reserved blocks). The same rule applies to the other PCD file system sizes / devices.

 

Categories

PCD3 / Mxxx

PCD7 / Rxxx

Last update: 27.05.2015 12:38

First release: 04.12.2008 12:38

Views: 4614

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download