Why is it not possible to use priority 6 for commandable objects?

FAQ #101017

Priority 6 is reserved for time operations for BACnet objects like minimum on time or minimum off time.

 

 

The BACnet properties "Minimum On Time" and "Minimum Off Time" use the field of priority 6 and overwrite the content inside if an on or off delay is used.

Therefore you should not use this priority.

 