Not possible to install PG5 1.4 on a PC with Windows 7 or on a PC on general

FAQ #100969

If during the installation of PG5 1.4 or SBC.Net Web-Connect there is an Error message: "Error 1606. Could not access network location WINDIR\system32", there could be two reasons for the cause.

 

Symptom
During the installation of PG5 1.4 on a PC with Windows 7 or SBC.Net Web-Connect on general there is following Error message:
Error 1606. Could not access network location WINDIR\system32

Possible reason 1
You have started the setup file of SBC.Net Web-Connect from a external server.
It’s not allowed to start the setup file of SBC.Net Web-Connect from an external server.

Solution 1
To solve the problem, copy the setup file of SBC.Net Web-Connect to your PC and start the setup file of SBC.Net Web-Connect locally on your PC.


Possible reason 2
You try to install PG5 1.4 on a PC with Windows 7.

Solution 2
It's very important to exactly follow the document "Installation Guide for PG5 1.4.300 on Windows 7 (64 bit)" out of the FAQ #100710 "Is PG5 1.4 compatible with Microsoft Windows Vista and Windows 7? ". In details to change the installation folder of PG5 1.4. Instead of "…\Saia_Burgess\PG5 1_4" add an underscore in "PG5_1_4".

 

Categories

PG5 1.x

WebConnect

Last update: 26.05.2015 19:27

First release: 20.06.2008 12:29

Views: 11655

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.