How can I modify the function presence of a standalone PCD7.L60x modules?
FAQ #100883
The first PCD7.L60x module series keeps the presence for 1 hour once the button "Presence" is pressed. It can't be desactivated manualy as it is done automatcaly after 1 hour!
This is the default parameter: R 0 = 6 (6 x 10 minutes).
Solution
In order to modify this default parameter connect over a S-Bus connection to the PCD7.L60x and modify the register 0 with the value 0 (instead of 6)! So one press on the presence button activates the presence and a 2nd press desactivate it!
Remark
The new PCD7.L60x have now as default the value 0 (since about begining 2008)!