RTS and CTS signs are crossed on Slot A#1 and A#2 (Hardware Version A and Prototypes) of the PCD2.M5540
FAQ #100831
Due to a hardware problem on the first pilot versions of the PCD2.M5540 the RTS and CTS are crossed.
Problem
The pilot versions and hardware version A of the PCD2.M5540 has the RTS and CTS sign crossed on terminal X3 and X4.
Reason
This happend due to a layout failure on the board on the PCD2.M5540 (Hardwareversion A and older)
Solution
Connect the RTS and CTS invers to the documentation if you have a concerned hardware.
Categories
PCD2 / M5xxx
Last update: 30.05.2015 08:55
First release: 21.11.2007 08:41