Why are broadcast telegramms not working anymore on the PCD3 or PCD2.M480
FAQ #100798
In firmware 03B and 03C an S-Bus broadcast telegram will block the communication interface until the next reboot of the PCD.
Symptom
When using firmware version 03B or 03C on either a PCD2.M480 or a PCD3.Mxxx0, the communication stops working after a sent broadcast. This only applies if the concerned PCD is acting as master on the S-Bus network.
This phenomenon occurs on S-Bus (Serial-S-Bus, Ether-S-Bus or Profi-S-Bus).
Reason
In firmware 03B and 03C an S-Bus broadcast telegram will block the communication interface until the next reboot of the PCD.
Solution
In order to resolve this problem, please update the firmware of your concerned PCD.
Categories
PCD2 / _Firmware Classic
PCD3 / Mxxx
PCD3 / _Firmware Classic
Communication / Ether-S-Bus
PG5 2.0 / Profi-S-Bus
PG5 2.0 / Serial-S-Bus
PCD2 / M48x
Last update: 30.05.2015 11:18
First release: 26.10.2007 12:22
Views: 9812