Why Profibus FMS doesn't work on PCD4.M445?

FAQ #100753

A user programme containing Profibus FMS configuration doesn't work on CPU0! It has to be downloaded on CPU 1 because this CPU bord contains the RS 485 Profibus FMS port!

 

Additionnaly: The virtual channel port for the SASSI and SCON instructions has to be chosen between 10 and 99!

For info on PCD2 and PCD7.F700 card it is channel 10 to 19!

More details can be found in the Profibus FMS Manual 26/742 on our Web Site!    

 

Categories

PCD4 / Mxxx

PCD7 / Fxxx

Last update: 10.04.2015 23:02

First release: 05.09.2007 12:10

Views: 3257

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.