PCD2.M480 FW 025: Not possible to go on line when Webserver is connected!

FAQ #100652

If a project Web Editor contains trends or alarms, it might not be possible to visualised the Web page and be online with PG5 simultaneously. In order to go online with the PCD a powerup is necessary!

The advanced functions aren't supported by this firmware version, this causes the disfunctionning!

 

Update the PCD with a nwer FW version at least B2B.  You can get the last firmware version from the support site.

 

Categories

PCD2 / M48x

Last update: 29.05.2015 21:53

First release: 21.12.2006 12:46

Views: 1647

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.