Callback of PCD7.R400 modules

FAQ #100641

The functionality of the PCD7.R400 produced in the time range between week 25 and week 47 in the year 2006 can not be guaranteed. Therefore a callback of these modules has been started.

 

Symptom
Among other effects it is not possible starting a restore of the content of an affected module by pressing the button on the module. Also the restore or backup of the memory from or to the PCD7.R400 is not reliable.

 

Reason
This problem is caused by a wrong flash chip mounted on the module (M29F800DB 70N1E instead of AM29F800BB-70ED). Please refer to the pictures below for identifying the relevant components (soldere right next to the button for a restore).

Correct flash chip Wrong flash chip; functionality not guaranteed!
image  image

Instructions to disassemble the PCD7.R400 for checking the flash chip:
image

Solution
You should have been contacted by your sales representative for calling back theses modules (the callback action was started in week 48 of 2006). If this is not the case, please contact your local Saia-Burgess Controls AG. representative and ask for the further procedure.

Detailed information about working combinations

PCD type Firmware Flash M29F8 (wrong) Flash AM29F8 (ok)
PCD2/4.M170 V017, V01A not working working
  ≥$18 or ≥ 020 working working
PCD2.M177 & SMART ≤ V3.116 not working working
  ≥ V3.117 (future) working working
PCD2.M480 010, 018, 020, 025 not working working
  ≥ 030 (future) working working
PCD2.M487 ≤ V1.314 not working working
  ≥ V1.346 (future) working working

Categories

PCD7 / Rxxx

Last update: 14.04.2015 01:57

First release: 04.12.2006 08:35

Views: 1938

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.