Why does the "Set Keypress" function not work?

FAQ #100583

It is not possible to initialise the belimo modules automatically.

 

Problem
It is not possible to initalise the Belimo components automatically. Returned error message is: "timeout"

 

Reason
This is a problem in the MP-Bus library. The initialise function does not work properly.

Solution
The problem will be fixed in the next official version.
As workaround the Belimo components can be configured manually by reading the number on the Belimo device and adding it in PG5. If you have a Belimo configuration equipment it is also possible to define it with the Belimo configuration equipment. Otherwise if both workarounds are not possible for you, you can ask us for the new bugfix library.

 

Categories

PG5 2.0 / MP-Bus

Last update: 30.05.2015 21:58

First release: 24.07.2006 13:16

Views: 1607

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.