What can cause problems when using the PCD8.K120
FAQ #100575
There are several point that can cause problems when using the Profi S-Link cable PCD8.K120.
Recommended firmware and PG5 version:
FW 023 or higher
PG5 1.4.100 or higher
With FW versions below 023 the power supply on the Profi S-IO connecter was not working.
Some improvments regarding the use of the Profi S-IO are implemented in PG5 1.4.100 or higer
Important point:
The Profi S-IO network needs termination resistants on both sides of the network, otherwise the connecting of the Profi S-Link adaptor will interrupt the communication on the bus. Note that if you are using Profibus connectors with internal termination resistant they have to be powered (plugged) otherwise the termination resistant is not active.