The clock of the PCD is incremented (1 hour) at each startup

FAQ #100550

This is a bug in the HEAVAC library.

 

Symptom
Each time when the PCD is restarted the clock of the PCD will be incremented 1 hour. This problem does only occur in the lasth week of the month March. 

 

Reason
This is a bug in the HEAVAC library and the problem appeard after the winter-summertime changing when the "Automatic change" is activated in the HEAVAC Init F-Box.

Solution
This problem is fixed in the FBox "Init 7" of the heavac library. In case the PCD is equipped with an older version of this FBox (e.g. Init 5), this FBox is to be replaced. The "Init 7" FBox that fixes the problem is distributed together with PG5 1.4.110 and later.

 

Categories

PG5 1.x

Last update: 30.05.2015 15:01