Why does the Fatal Error 377 appears on build

FAQ #100545

If under Settings/Software/Advanced the option: no "Software Settings" file is activated this error can appear.

 

Problem
A disassembled file without "Software Settings" file generates the following message on build:
Fatal Error 377: No $AUTO declaration for type: R

Reason
In an other file a global symbol with dynamic addressing is present. Even if the file is not linked the global symbol will cause this error.

Solution
Delete the dynamic addressed symbol or work with "Software Settings" file.

 

Categories

PG5 1.x

Last update: 30.05.2015 20:51

First release: 16.03.2006 10:17

Views: 626

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download